• DocumentCode
    2317227
  • Title

    A review of artificial contamination withstand test methods of high voltage outdoor insulators

  • Author

    Naderian, Ali ; Sanaye-Pasand, Majid ; Mohseni, Hosein

  • Author_Institution
    ECE Dept., Tehran Univ., Iran
  • fYear
    2004
  • fDate
    19-22 Sept. 2004
  • Firstpage
    284
  • Lastpage
    287
  • Abstract
    In This work several important test methods for artificially polluted ceramic and nonceramic insulators have been reviewed. There is no standard test for nonceramic insulators. The research has shown that it is necessary to modify the standard 5000 h salt fog test to evaluate the long-term performance of nonceramic insulators. Although the main parameter for selection of proper ceramic and glass insulators is the amount of pollution, it seems to be necessary to consider other environmental factors for selection of composite insulators. These are average humidity, UV radiation level, wind velocity, rain fall, and dominant type of wetting. This is necessary because research has shown that they directly effect the performance of nonceramic insulators.
  • Keywords
    ceramic insulators; composite insulators; environmental factors; insulator contamination; insulator testing; UV radiation; artificially polluted ceramic insulators; artificially polluted nonceramic insulators; composite insulators; environmental factors; glass insulators; high voltage outdoor insulators; humidity; salt fog test; wind velocity; Ceramics; Contamination; Environmental factors; Glass; Humidity; Insulation; Insulator testing; Pollution; Voltage; Wind speed;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380559
  • Filename
    1380559