• DocumentCode
    2317353
  • Title

    Evaluation of 23 kV insulator profiles with different pollution levels

  • Author

    Herndndez-Corona, R. ; Ramirez- Vazquez, I. ; Montoya-Tena, Gerardo

  • Author_Institution
    Inst. de Investigaciones Electricas, Cuernavaca, Mexico
  • fYear
    2004
  • fDate
    19-22 Sept. 2004
  • Firstpage
    304
  • Lastpage
    307
  • Abstract
    Insulators used for 23 kV distribution lines working under high pollution conditions were removed from field. These insulators were evaluated in a fog chamber. The results showed that the insulator profile has a strong effect on the performance of the insulator under very heavy pollution and humidity conditions. Insulators having a simple profile electrically failed under light pollution conditions. While, insulators having a complex profile did not fail under very heavy pollution conditions. The results obtained for each insulator evaluated are presented in This work.
  • Keywords
    fog; insulator contamination; insulator testing; power distribution lines; 23 kV; distribution lines; fog chamber; humidity conditions; insulator profiles; pollution conditions; Dielectrics and electrical insulation; Flashover; Humidity; Laboratories; Measurement standards; Pollution measurement; Sea level; Surface contamination; Urban pollution; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380565
  • Filename
    1380565