AC withstand voltage performance of 110 kV iced composite insulators
Author
Hu, Jianlin ; Shu, Lichun ; Sun, Caixin ; Jiang, Xingliang ; Sima, Wenxia
Author_Institution
Key. Lab. of High Voltage Eng. & Electr. New Technol., Chongqing Univ., China
fYear
2004
fDate
19-22 Sept. 2004
Firstpage
343
Lastpage
346
Abstract
Based on the test results performed on 110 kV FXBW-110/100 iced composite insulators with a withstand voltage method in the multifunction artificial climate chamber of Chongqing University, this paper indicates that the withstand duration for an iced composite insulator should be at least 15 minutes, and that at normal conditions, all the tested insulators iced with a freezing water conductivity of 300 μS/cm can withstand the service voltage. This paper analyzes the effect of the atmospheric pressure on withstand and flashover voltages. Because the discharge path has a high randomness, the effect of atmospheric pressure on flashover voltages of iced insulators has a high randomness.
Keywords
atmospheric pressure; composite insulators; flashover; freezing; ice; insulator testing; 110 kV; Chongqing University; FXBW-110/100 iced composite insulators; artificial climate chamber; atmospheric pressure; discharge path; flashover voltages; freezing water conductivity; voltage performance; Dielectrics and electrical insulation; Flashover; Ice; Insulation testing; Insulator testing; Performance evaluation; Power transmission lines; Rain; Spraying; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
ISSN
1089-084X
Print_ISBN
0-7803-8447-4
Type
conf
DOI
10.1109/ELINSL.2004.1380584
Filename
1380584
Link To Document