ldquoResidual charge methodrdquo, which has been developed for detection of non-bridged water tree, is well known as a high reliability water tree deterioration diagnosis technique for XLPE cable, and it has been applied for on-site cable system diagnosis. Traditional residual charge method measures the amount of electrical charge, and the information of cable length is required to evaluate the result. In this paper, we would like to introduce our development of the new technique of residual charge method which does not need the information of cable length to evaluate the deterioration degree.
Keywords
XLPE insulation; cable insulation; fault diagnosis; power cable insulation; trees (electrical); XLPE cable; electrical charge; residual charge method; water tree deterioration diagnosis; Cables; Capacitors; Charge measurement; Circuits; Conductivity; Permittivity; Power system reliability; Trees - insulation; Vehicles; Voltage; XLPE cable; deterioration diagnosis; residual charge method; water tree;