Title :
Application of combined PD sensor for GIS PD detection and condition monitoring
Author :
Min, Chen ; Urano, Koji ; You-Cheng, Li ; Jinno, Atsuhide
Author_Institution :
SE Technol. Ltd., Hong Kong
Abstract :
It was reported previously that partial discharge (PD) existing in GIS can be localized with a PD localization method based on the time difference of PD detection, in which more than one pulse current sensors are installed at the GIS sealing end or cable termination. However, the localization accuracy is not satisfactory since the PD propagation speed is too high and not average inside GIS. To increase the accuracy combined PD sensors to detect pulse current and to catch the acoustic signal were applied for the on-site PD localization. The result shows that higher location accuracy can be obtained.
Keywords :
acoustic emission; condition monitoring; current transformers; gas insulated switchgear; partial discharge measurement; sensors; GIS PD detection; GIS sealing end; PD localization method; PD propagation speed; acoustic emission sensor; acoustic signal; cable termination; capacitive coupling sensor; combined PD sensor; condition monitoring; gas insulated switchgear; high frequency current transformer; partial discharge; pulse current sensors; Acoustic emission; Acoustic pulses; Acoustic sensors; Acoustic signal detection; Capacitive sensors; Carbon capture and storage; Condition monitoring; Geographic Information Systems; Partial discharges; Sensor systems; AE sensor (AES); GIS; PD localization (PDL); PD measurement (PDM); acoustic emission (AE); capacitive coupling sensor (CCS); combined PD sensor; high frequency current transformer (HFCT); partial discharge (PD); spacer;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580324