Title :
Electrical and Thermal Analysis of Parallel Single-Conductor Cable Installations
Author :
Du, Y. ; Wang, X.H.
Author_Institution :
Dept. of Building Services Eng., Hong Kong Polytech. Univ., Hong Kong, China
Abstract :
The unequal current distribution in parallel single-conductor cable installations can lead to an excessive temperature rise. This paper presented a cable model and a procedure of coupled electrical and thermal analysis for the evaluation of currents, losses and temperatures in the cables of concern. The cable model and analytic method were validated experimentally in the laboratory. The procedure was applied to evaluate the current rating, the temperature rise in a particular single-conductor installation. It is concluded that the parallel cable installation without proper cable rephrasing de-rates the cables significantly. The 3rd order harmonic current can cause a significant reduction of the current rating if its distortion is over 30%.
Keywords :
cables (electric); conductors (electric); electric properties; thermal analysis; electrical analysis; parallel single conductor cable installation; single conductor installation; thermal analysis; third order harmonic current; Cable insulation; Circuits; Current distribution; Finite element methods; Frequency; Power cable insulation; Power cables; Temperature distribution; Thermal resistance; Transformers;
Conference_Titel :
Industry Applications Society Annual Meeting, 2009. IAS 2009. IEEE
Conference_Location :
Houston, TX
Print_ISBN :
978-1-4244-3475-6
Electronic_ISBN :
0197-2618
DOI :
10.1109/IAS.2009.5324885