DocumentCode :
2319354
Title :
The experience of DP and furan in remnant life assessment of power transformer
Author :
Baburao, K. ; Bhangre, NM ; Wagle, AM ; Venkatasami, A. ; Chaudhari, Sushil E.
Author_Institution :
CG Global R&D Centre, Crompton Greaves Ltd., Mumbai
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
555
Lastpage :
558
Abstract :
Transformer life depends on the life of the oil impregnated paper insulation system. Degradation of the cellulose insulation is an irreversible process. Chemical reaction of cellulose cause opening of glucose rings providing free glucose molecules, water, CO2 and organic acids. These glucose monomers further decompose and produce furanic compounds as end products. DP and furan tests are used to identify the extent of ageing of the cellulose in paper insulation of the transformer. Many authors including Chendong.I, have reported the empirical relations relating furan content with DP. These empirical relations are finding application in estimating the consumed life of the transformer. We are doing extensive DP and furan analyses for remnant life assessment of transformers. This paper reports our experiences with DP and Furan as a diagnostics tool as applied to a high voltage transformer. Our data is based on the DP test results conducted on the samples collected at various strategic locations such as main lead, canopy, barrier boards etc. The furan data collected over several years were analyzed. The past trend is used to determine the deterioration rate. All these results are correlated and the same is presented in this article.
Keywords :
ageing; carbon compounds; paper; permittivity; potential transformers; power transformers; remaining life assessment; thermal analysis; transformer oil; CO2; Furan analyses; Remnant life assessment; ageing; cellulose insulation; chemical reaction; glucose monomers; high voltage transformer; paper insulation system; power transformer; Aging; Insulation testing; Life estimation; Oil insulation; Organic chemicals; Petroleum; Power transformer insulation; Power transformers; Sugar; Thermal degradation; DGA; Degree of Polymerization (DP); FTIR; Furan; HPLC; Impregnated paper; Power transformer; Press board; Transformer Oil; Wood;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
Type :
conf
DOI :
10.1109/CMD.2008.4580348
Filename :
4580348
Link To Document :