Abstract :
This paper presents some practical experience of polarisation/depolarisation current (PDC) analysis on a number of condenser bushings having three different insulation designs-oil impregnated paper (OIP), synthetic resin bonded paper (SRBP) and resin impregnated paper (RIP). It suggests methods for performing successful on-site measurement. The document contains PDC measurement results and evaluation results of main insulation C1 for each type of bushing. It proves that the sensitivity in detecting insulation aging of the PDC technique is better than the conventional 50 Hz test.
Keywords :
ageing; bushings; condition monitoring; impregnated insulation; partial discharge measurement; polarisation; resins; transformer oil; 50 Hz; PDC measurement; condenser bushings; insulation aging; insulation condition assessment; insulation designs; oil impregnated paper; on-site measurement; polarisation-depolarisation current analysis; resin impregnated paper; synthetic resin bonded paper; transformer bushings; Bonding; Insulators; Moisture; Oil insulation; Petroleum; Polarization; Power transformer insulation; Power transformers; Resins; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
ISSN :
1089-084X
Print_ISBN :
0-7803-8447-4
Type :
conf
DOI :
10.1109/ELINSL.2004.1380664
Filename :
1380664
Link To Document :
بازگشت