DocumentCode
2319614
Title
On-line insulation diagnostics for current transformers
Author
Evert, Richard ; Hoch, Derek
fYear
2004
fDate
19-22 Sept. 2004
Firstpage
512
Lastpage
517
Abstract
High voltage current transformers (CTs) perform a secondary function in a power utility. In the Transmission group in Eskom, more than 30% of over 10000 CTs have been in service for more than 30 years. A real need exists for a method by which on-line partial discharge (pd) measurements can be recorded which translate into a qualitative interpretation of the degree to which both bulk insulation deterioration and voids have progressed with operational conditions. This paper will present the concepts of high frequency elements in the insulation leakage current which uniquely describe different types of failure modes in high voltage insulation. The paper will present results of forcibly created voids and insulation deterioration and the corresponding signatures for these conditions.
Keywords
current transformers; failure analysis; partial discharge measurement; power transformer insulation; transformer oil; CT; Eskom transmission group; failure modes; high frequency elements; high voltage current transformers; high voltage insulation; insulation deterioration; insulation leakage current; on-line insulation diagnostics; partial discharge measurement; power utility; qualitative interpretation; Africa; Current transformers; Dielectrics and electrical insulation; Frequency; Insulation life; Laboratories; Partial discharges; Power transformer insulation; Testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
ISSN
1089-084X
Print_ISBN
0-7803-8447-4
Type
conf
DOI
10.1109/ELINSL.2004.1380670
Filename
1380670
Link To Document