DocumentCode
2320709
Title
FRA low frequency characteristic study using duality transformer core modeling
Author
Peng Ang, Swee ; Li, Jie ; Wang, Zhongdong ; Jarman, Paul
Author_Institution
Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester
fYear
2008
fDate
21-24 April 2008
Firstpage
889
Lastpage
893
Abstract
In this paper a simulation model for a three-phase, three-limb core-type 1000 MVA 400/275/13 kV autotransformer is presented to study Frequency Response Analysis (FRA). The equivalent electric circuit of the magnetic core is derived based on the Principle of Duality. Leakage inductances and capacitances of windings are also included in the model. All the parameters are determined using manufacturer data sheet. FRA simulation results up to 1 kHz are validated by the measurement results. The FRA low frequency characteristics of transformers are first time explained through modeling and the dominating parameters for these characteristics identified.
Keywords
equivalent circuits; frequency response; transformer cores; core-type autotransformer; duality transformer core; equivalent electric circuit; frequency response analysis; low frequency characteristic; magnetic core; three-limb autotransformer; three-phase autotransformer; voltage 13 kV; voltage 275 kV; voltage 400 kV; Analytical models; Capacitance; Circuit simulation; Frequency response; Magnetic analysis; Magnetic circuits; Magnetic cores; Manufacturing; Transformer cores; US Department of Transportation; Antiresonance and Resonance; Frequency Response Analysis (FRA); Power Transformers; Principle of Duality; Three-limb core;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-1621-9
Electronic_ISBN
978-1-4244-1622-6
Type
conf
DOI
10.1109/CMD.2008.4580426
Filename
4580426
Link To Document