Title :
Transfer function as tool for noise suppression and localization of partial discharges in transformers during on-site measurements
Author :
Gockenbach, E. ; Borsi, H.
Author_Institution :
Schering-Inst., Leibniz Univ. Hannover, Hannover
Abstract :
Partial discharge (PD) measurements are one the most important non destructive test methods to evaluate the integrity of the insulation system of power transformers. PD measurements on site are strongly influenced by noise and besides the level of the PD activity the location of the PD source is of importance. Using the well known transfer function from transformer impulse tests the variation of the PD signal travelling trough the transformer winding are the basis for the separation between noise and PD signals and also for the localization of the PD source. Laboratory tests show very good results. With a simple capacitive coupler and signal transmission via fibre optic cable the system can also be used satisfactorily on site.
Keywords :
interference suppression; partial discharge measurement; power transformer insulation; power transformer testing; transfer functions; transformer windings; capacitive coupler; fibre optic cable; insulation system; noise suppression; nondestructive test methods; on-site measurements; partial discharge measurements; power transformers; signal transmission; transfer function; transformer winding; Insulation testing; Noise level; Noise measurement; Partial discharge measurement; Partial discharges; Power measurement; Power transformer insulation; Power transformers; System testing; Transfer functions; High voltage technique; Localization; Noise suppression; Partial Discharge measurement;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580478