  • Abstract
    Partial discharge (PD) analysis is a reliable tool to assess the integrity of electrical insulation. Representation and interpretation of the data, obtained from e.g. online PD monitoring, are key issues to reveal the discharge source, i.e. defect type, as well as the physical phenomena behind the occurrence. Analyses of various PD patterns such as discharge height distribution presented in this work provide useful statistical parameters to identify the discharge source. Research shows that the 2-parameter Weibull distribution is a reliable model to quantify the characteristics of the patterns of the defect. The model fits well to the charge-height distribution. In addition, trends in the discharge density pattern that occur over long times, can be used as complementary information to discover the discharge nature. It alerts for a possible failure and therefore assists in taking corrective measures to prevent failure. This paper presents the application of such statistical modeling to the area of on-line power cable diagnostics. Data obtained from laboratory experiments as well as field data have been studied.
  • Keywords
    Weibull distribution; partial discharges; power cable insulation; 2-parameter Weibull distribution; MV cables; charge-height distribution; discharge density pattern; discharge height distribution; discharge source; electrical insulation; online PD monitoring; online power cable diagnostics; partial discharge; statistical approach; statistical modeling; Condition monitoring; Dielectrics and electrical insulation; Electric breakdown; Failure analysis; Fault location; Partial discharges; Performance evaluation; Power cables; Statistical analysis; Weibull distribution; monitoring; partial discharges; power cable; power cable insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580504
  • Filename
    4580504