DocumentCode
2322065
Title
A study on the measurement of partial discharges in XLPE power cables using planer loop sensors
Author
Lim, Kwang-Jin ; Lwin, Kyaw-Soe ; Shin, Dong-Hoon ; Park, Noh-Joon ; Park, Dae-Hee ; Hwang, Doo-Hyun ; Lim, Jong-Cheon
Author_Institution
Wonkwang Univ., Iksan
fYear
2008
fDate
21-24 April 2008
Firstpage
1216
Lastpage
1219
Abstract
This study designed a new type of loop antenna that is able to detect partial discharges based on microstrip line technology. In diagnosis of power cables, partial discharge signals are generally produced at a frequency range less than 100 MHz because high frequency PD signals are lost along a propagation path in such cables. In partial discharge measurement experiments, a commercial HFCT sensor was used as a reference sensor. Several experiments were made over HFCT and loop antenna sensors for detecting partial discharges on 22.9 kV MV XLPE cable. In this study, we showed the loop antenna designed in this study that can be applied as a commercial HFCT sensor.
Keywords
XLPE insulation; loop antennas; microstrip lines; partial discharge measurement; power cable insulation; HFCT sensor; XLPE power cables; loop antenna; microstrip line technology; partial discharges; planer loop sensors; Antenna measurements; Antennas and propagation; Frequency; Metalworking machines; Microstrip antennas; Microstrip components; Partial discharge measurement; Partial discharges; Power cables; Power measurement; HFCT sensor; Partial Discharges; microstrip line technology; power cables;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-1621-9
Electronic_ISBN
978-1-4244-1622-6
Type
conf
DOI
10.1109/CMD.2008.4580507
Filename
4580507
Link To Document