DocumentCode :
2322065
Title :
A study on the measurement of partial discharges in XLPE power cables using planer loop sensors
Author :
Lim, Kwang-Jin ; Lwin, Kyaw-Soe ; Shin, Dong-Hoon ; Park, Noh-Joon ; Park, Dae-Hee ; Hwang, Doo-Hyun ; Lim, Jong-Cheon
Author_Institution :
Wonkwang Univ., Iksan
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1216
Lastpage :
1219
Abstract :
This study designed a new type of loop antenna that is able to detect partial discharges based on microstrip line technology. In diagnosis of power cables, partial discharge signals are generally produced at a frequency range less than 100 MHz because high frequency PD signals are lost along a propagation path in such cables. In partial discharge measurement experiments, a commercial HFCT sensor was used as a reference sensor. Several experiments were made over HFCT and loop antenna sensors for detecting partial discharges on 22.9 kV MV XLPE cable. In this study, we showed the loop antenna designed in this study that can be applied as a commercial HFCT sensor.
Keywords :
XLPE insulation; loop antennas; microstrip lines; partial discharge measurement; power cable insulation; HFCT sensor; XLPE power cables; loop antenna; microstrip line technology; partial discharges; planer loop sensors; Antenna measurements; Antennas and propagation; Frequency; Metalworking machines; Microstrip antennas; Microstrip components; Partial discharge measurement; Partial discharges; Power cables; Power measurement; HFCT sensor; Partial Discharges; microstrip line technology; power cables;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
Type :
conf
DOI :
10.1109/CMD.2008.4580507
Filename :
4580507
Link To Document :
بازگشت