• DocumentCode
    2322065
  • Title

    A study on the measurement of partial discharges in XLPE power cables using planer loop sensors

  • Author

    Lim, Kwang-Jin ; Lwin, Kyaw-Soe ; Shin, Dong-Hoon ; Park, Noh-Joon ; Park, Dae-Hee ; Hwang, Doo-Hyun ; Lim, Jong-Cheon

  • Author_Institution
    Wonkwang Univ., Iksan
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    1216
  • Lastpage
    1219
  • Abstract
    This study designed a new type of loop antenna that is able to detect partial discharges based on microstrip line technology. In diagnosis of power cables, partial discharge signals are generally produced at a frequency range less than 100 MHz because high frequency PD signals are lost along a propagation path in such cables. In partial discharge measurement experiments, a commercial HFCT sensor was used as a reference sensor. Several experiments were made over HFCT and loop antenna sensors for detecting partial discharges on 22.9 kV MV XLPE cable. In this study, we showed the loop antenna designed in this study that can be applied as a commercial HFCT sensor.
  • Keywords
    XLPE insulation; loop antennas; microstrip lines; partial discharge measurement; power cable insulation; HFCT sensor; XLPE power cables; loop antenna; microstrip line technology; partial discharges; planer loop sensors; Antenna measurements; Antennas and propagation; Frequency; Metalworking machines; Microstrip antennas; Microstrip components; Partial discharge measurement; Partial discharges; Power cables; Power measurement; HFCT sensor; Partial Discharges; microstrip line technology; power cables;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580507
  • Filename
    4580507