• DocumentCode
    2322127
  • Title

    Partial discharge classification and diagnosis of power cable joint by statistical processing

  • Author

    Cho, Kyung-Soon ; Shin, Jong-Yeol ; Lee, Young-Sang ; Lee, Hyuk-Jin ; Hong, Jin-woong

  • Author_Institution
    Seoul Coll., Seoul
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    1232
  • Lastpage
    1235
  • Abstract
    The prefabricated type used generally in Korea to join cable runs on new installations, because installation is very simple and save time. This type is a permanent, shielded and submersible cable joint for direct burial or vault application. It confirms to the requirements of IEEE std. 404-2004 by factory testing, but many problems of insulated cable systems are caused by internal defects of the joint part which have to be mounted onsite. Faults arise from impurities or voids. A suitable solution for a monitoring of cable joints during the after-laying test and service is partial discharge detection. This paper described the influence on partial discharge distribution of various defects at the model power cable joints interface by statistical processing. As the result of analyzing Phi-q-n patterns, several parameters i. e. maximum discharge qmax, average discharge q and average angle of discharge thetasg were found to depend upon the defect type varying applied voltage. As the result of analyzing discharge number distribution of Phi-n cluster using K-means clustering, clusters shifted to 0deg and 180deg with increasing applying voltage. It was confirmed that discharge quantity and Euclidean distance between centroids were increased with applying voltage from the analyzing centroid distribution of Phi-q cluster.
  • Keywords
    IEEE standards; cable jointing; partial discharges; power cable testing; statistical analysis; Euclidean distance; IEEE std. 404-2004; K-means clustering; Phi-q-n patterns; after-laying test; discharge quantity; factory testing; insulated cable systems; partial discharge classification; partial discharge diagnosis; power cable joints; statistical processing; Cable insulation; Cable shielding; Impurities; Partial discharges; Power cable insulation; Power cables; Production facilities; System testing; Underwater vehicles; Voltage; EPR; K-means; PD classification; cable joint; diagnosis; statistical processing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580511
  • Filename
    4580511