DocumentCode
2322401
Title
The impact of TCSC on distance protection relay
Author
Weiguo, Wang ; Xianggen, Yin ; Jiang, Yu ; Xianzhong, Duan ; Deshu, Chen
Author_Institution
Huazhong Univ. of Sci. & Technol., Wuhan, China
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
382
Abstract
When a fault occurs in thyristor controlled series compensation (TCSC) transmission lines, TCSC presents a very complicated impedance characteristic and exerts influence on the power system´s distance relays. Under ground faults, the complex changes of sequence currents exert influences on the mho characteristic, reactance characteristic and directional characteristic and makes the protection region unstable. Longitude distance protection with an overreaching setting value may be a solution to TCSC line´s protection, but it has difficulty in setting the relay on the reverse directional line to avoid misoperation. Simulation shows that sampling frequency has an influence on distance protection performance in TCSC transmission lines
Keywords
compensation; flexible AC transmission systems; power capacitors; power system relaying; power transmission control; power transmission faults; power transmission lines; power transmission protection; reactive power control; relay protection; thyristor circuits; AC transmission lines; FACTS; TCSC; directional characteristic; distance protection relay; ground faults; impedance characteristic; mho characteristic; reactance characteristic; thyristor controlled series compensation; unstable protection region; Control systems; Impedance; Power capacitors; Power system faults; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Sampling methods; Thyristors;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.728991
Filename
728991
Link To Document