DocumentCode :
2322874
Title :
A survey of the flashover performance of HVDC converter station insulators
Author :
Almgren, Bengt ; Åström, Urban ; Wu, Dong
Author_Institution :
ABB Power Syst., Ludvika, Sweden
Volume :
1
fYear :
1998
fDate :
18-21 Aug 1998
Firstpage :
516
Abstract :
The operational experience of most of the HVDC converter stations in the world has been investigated, summarized and analyzed with regard to external flashovers across station insulators and apparatus. At some stations, some of the insulators have caused several flashovers soon after commissioning. The maximum flashover frequency occurred between 1987-1989, totalling about 20 flashovers per year at the 24 to 32 stations in operation. Several efficient countermeasures or maintenance methods have been developed. After the introduction of such measures, flashover frequency has normally been reduced to almost zero. During the last four years, the number of flashovers per converter station has been about 0.10, corresponding to about 0.05 per pole
Keywords :
HVDC power convertors; flashover; insulator testing; maintenance engineering; substations; HVDC converter station insulators; flashover frequency; flashover performance; maintenance methods; Contamination; Extraterrestrial measurements; Flashover; Frequency; HVDC transmission; Insulation; Pollution measurement; Power system analysis computing; Rivers; Statistics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location :
Beijing
Print_ISBN :
0-7803-4754-4
Type :
conf
DOI :
10.1109/ICPST.1998.729017
Filename :
729017
Link To Document :
بازگشت