• DocumentCode
    2326452
  • Title

    Analysis of large turbogenerator´s asynchronous operation during loss of field

  • Author

    Guo, K.Z. ; Zhu, W.D. ; Tan, F.W. ; Jin, R.L. ; Wang, G.

  • Author_Institution
    Shanghai Jiaotong Univ., China
  • Volume
    2
  • fYear
    1998
  • fDate
    18-21 Aug 1998
  • Firstpage
    935
  • Abstract
    The author studies the impedance of eddy current circuits for the solid rotor of a turbogenerator by Canay´s formulation. The mathematical model of variable parameters, which change with slip, is obtained by applying Canay´s calculating formulas. Simulation of field failure for the 125/900 MW turbogenerator set on infinite system, inclusively of governor, automatic voltage regulator, transformer and transmission line, is respectively analyzed. The calculated variables, such as the changing amplitude, period, and waveforms of power and reactive power, are relatively close to oscillograms and data measured at site. The conclusion of this article can be used as a reference for the operation of a power system
  • Keywords
    eddy currents; electric impedance; failure analysis; machine theory; reactive power; rotors; turbogenerators; 125 MW; 900 MW; Canay´s formulation; active power waveforms; automatic voltage regulator; eddy current circuits impedance; field failure simulation; loss of field; mathematical model; oscillograms; reactive power waveforms; solid rotor; transformer; transmission line; turbogenerator asynchronous operation; Analytical models; Circuit simulation; Eddy currents; Failure analysis; Impedance; Mathematical model; Power transmission lines; Regulators; Solids; Turbogenerators;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    0-7803-4754-4
  • Type

    conf

  • DOI
    10.1109/ICPST.1998.729222
  • Filename
    729222