DocumentCode
2326452
Title
Analysis of large turbogenerator´s asynchronous operation during loss of field
Author
Guo, K.Z. ; Zhu, W.D. ; Tan, F.W. ; Jin, R.L. ; Wang, G.
Author_Institution
Shanghai Jiaotong Univ., China
Volume
2
fYear
1998
fDate
18-21 Aug 1998
Firstpage
935
Abstract
The author studies the impedance of eddy current circuits for the solid rotor of a turbogenerator by Canay´s formulation. The mathematical model of variable parameters, which change with slip, is obtained by applying Canay´s calculating formulas. Simulation of field failure for the 125/900 MW turbogenerator set on infinite system, inclusively of governor, automatic voltage regulator, transformer and transmission line, is respectively analyzed. The calculated variables, such as the changing amplitude, period, and waveforms of power and reactive power, are relatively close to oscillograms and data measured at site. The conclusion of this article can be used as a reference for the operation of a power system
Keywords
eddy currents; electric impedance; failure analysis; machine theory; reactive power; rotors; turbogenerators; 125 MW; 900 MW; Canay´s formulation; active power waveforms; automatic voltage regulator; eddy current circuits impedance; field failure simulation; loss of field; mathematical model; oscillograms; reactive power waveforms; solid rotor; transformer; transmission line; turbogenerator asynchronous operation; Analytical models; Circuit simulation; Eddy currents; Failure analysis; Impedance; Mathematical model; Power transmission lines; Regulators; Solids; Turbogenerators;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729222
Filename
729222
Link To Document