DocumentCode
2326907
Title
Improvement of permissible loading of transformers
Author
Schlabbach, J.
Author_Institution
Appl. Sci. Univ., Bielefeld, Germany
Volume
2
fYear
2003
fDate
22-24 Sept. 2003
Firstpage
305
Abstract
The permissible loading of transformers is determined by internal losses, radiated heat from sun exposure and radiation and convection heat losses. In countries with high temperatures and high solar radiation, the transformer rating can be increased by solar shield preventing the heating through solar radiation. For 237 transformers (HV/MV) the influencing factors are discussed and analyzed and a cost comparison and economic evaluation was carried out. The results indicated that solar shielding is applicable for transformers with rating above 18MVA, as the cost for the shields will be lower than the cost benefit for the expected transformer life time of 20 years.
Keywords
cost-benefit analysis; load flow control; solar radiation; transformers; convection heat losses; cost benefit; internal losses; permissible loading; solar radiation; solar shield; sun exposure; transformer loading; transformers; Cooling; Costs; Heat transfer; Oil insulation; Power transformer insulation; Solar heating; Solar radiation; Substations; Sun; Temperature;