  • Abstract
    The paper presents a study of single-phase auto-reclosing of the Vietnam 500 kV transmission system. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influence of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive couplings and series capacitor discharge on the extinction of the secondary arc is investigated. The paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnamese power system. Finally, methods to increase the success of the single-phase auto-reclosing scheme also are investigated
  • Keywords
    circuit-breaking arcs; power system transient stability; power transmission protection; transmission networks; 500 kV; capacitive couplings; fault location; faulted phase; inductive couplings; neutral reactors; secondary arc extinction; series capacitor discharge; shunt reactors; single-phase auto-reclosing; transient stability; transmission system protection; Capacitors; Cities and towns; Couplings; Inductors; Power generation; Power system stability; Power system transients; Power transmission lines; Shunt (electrical); Zero voltage switching;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    0-7803-4754-4
  • Type

    conf

  • DOI
    10.1109/ICPST.1998.729251
  • Filename
    729251