DocumentCode
2327008
Title
Single-phase auto-reclosing of the Vietnam 500 kV system
Author
Tran-Quoc, T. ; Huy, H. Vo V ; Lan, H. Duong ; Nguyen-T.-Hoang, L. ; Dinh, L. Tran
Author_Institution
Lab. d´´Electrotech. de Grenoble, Saint Martin d´´Heres, France
Volume
2
fYear
1998
fDate
18-21 Aug 1998
Firstpage
1077
Abstract
The paper presents a study of single-phase auto-reclosing of the Vietnam 500 kV transmission system. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influence of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive couplings and series capacitor discharge on the extinction of the secondary arc is investigated. The paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnamese power system. Finally, methods to increase the success of the single-phase auto-reclosing scheme also are investigated
Keywords
circuit-breaking arcs; power system transient stability; power transmission protection; transmission networks; 500 kV; capacitive couplings; fault location; faulted phase; inductive couplings; neutral reactors; secondary arc extinction; series capacitor discharge; shunt reactors; single-phase auto-reclosing; transient stability; transmission system protection; Capacitors; Cities and towns; Couplings; Inductors; Power generation; Power system stability; Power system transients; Power transmission lines; Shunt (electrical); Zero voltage switching;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729251
Filename
729251
Link To Document