DocumentCode
2327291
Title
Affection of distributed capacitance on and a new method of detecting on detecting DC system earth fault
Author
Jia, Xiufang ; Zhao, Chengyong ; Li, Baoshu
Author_Institution
Dept. of Electr. Power Eng., North China Electr. Power Univ., Hebei, China
Volume
2
fYear
1998
fDate
18-21 Aug 1998
Firstpage
1168
Abstract
On the basis of discussing the existing detecting principle of earth faults in a DC system, the paper analyzes relation of earth resistance, signal frequency, and earth distributed capacitance of a DC system. Two mathematical equations are derived for earth resistance as the function of distributed capacitance in criterion on resistance current and that on the comparison between ratios of currents. Explicit data relations are given. At the same time the paper discusses the effect of the principle on undulation coefficient of DC voltage also. Finally, a new method of detecting an earth fault is introduced, which need not feed low frequency AC voltage signal into DC bus by the principle of magnetic modulation
Keywords
DC power transmission; capacitance; electric resistance; power transmission faults; DC system earth fault detection; distributed capacitance; earth distributed capacitance; earth resistance; mathematical equations; signal frequency; undulation coefficient; Capacitance; Circuit faults; Earth; Electrical fault detection; Fault detection; Frequency; Insulation; Monitoring; Signal generators; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729269
Filename
729269