• DocumentCode
    2339346
  • Title

    Manufacture and experiment of a novel composite insulator

  • Author

    Lu, Jiazheng ; Zhao, Chun ; Li, Bo ; Jiang, Zhenglong ; Fang, Zhen ; Zhang, Hongxian

  • Author_Institution
    Power Transm. & Distrib. Equip. Anti-icing & Reducing-disaster Technol. Lab., Hunan Electr. Power Corp. Res. Inst., Changsha, China
  • Volume
    1
  • fYear
    2011
  • fDate
    22-23 Oct. 2011
  • Firstpage
    127
  • Lastpage
    130
  • Abstract
    Serious lightning or icing often causes flashover on the insulators and probably results in a tripping accident. A novel composite insulator with lightning protection and icing flashover prevention is presented. The novel composite insulator with the rated voltage of 220 kV, specified mechanical load of 100 kN for the whole insulator and the nominal discharge current of 10 kA for the lightning protection part is designed and is manufactured. Basic performance, electrical performance, and mechanical performance are tested for the novel composite insulator. The experimental results show that the novel product meets the requirements of both standards of the common composite insulator and the common line metal oxide surge arrester and achieves the application conditions.
  • Keywords
    arresters; composite insulators; lightning protection; composite insulator; current 10 kA; electrical performance; flashover; lightning protection; mechanical performance; metal oxide surge arrester; tripping accident; voltage 220 kV; Accidents; Area measurement; Heating; Insulators; Lightning; composite insulator; icing flashover prevention; lightning protection; zinc oxide varistor;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    System Science, Engineering Design and Manufacturing Informatization (ICSEM), 2011 International Conference on
  • Conference_Location
    Guiyang
  • Print_ISBN
    978-1-4577-0247-1
  • Type

    conf

  • DOI
    10.1109/ICSSEM.2011.6081162
  • Filename
    6081162