DocumentCode :
2339346
Title :
Manufacture and experiment of a novel composite insulator
Author :
Lu, Jiazheng ; Zhao, Chun ; Li, Bo ; Jiang, Zhenglong ; Fang, Zhen ; Zhang, Hongxian
Author_Institution :
Power Transm. & Distrib. Equip. Anti-icing & Reducing-disaster Technol. Lab., Hunan Electr. Power Corp. Res. Inst., Changsha, China
Volume :
1
fYear :
2011
fDate :
22-23 Oct. 2011
Firstpage :
127
Lastpage :
130
Abstract :
Serious lightning or icing often causes flashover on the insulators and probably results in a tripping accident. A novel composite insulator with lightning protection and icing flashover prevention is presented. The novel composite insulator with the rated voltage of 220 kV, specified mechanical load of 100 kN for the whole insulator and the nominal discharge current of 10 kA for the lightning protection part is designed and is manufactured. Basic performance, electrical performance, and mechanical performance are tested for the novel composite insulator. The experimental results show that the novel product meets the requirements of both standards of the common composite insulator and the common line metal oxide surge arrester and achieves the application conditions.
Keywords :
arresters; composite insulators; lightning protection; composite insulator; current 10 kA; electrical performance; flashover; lightning protection; mechanical performance; metal oxide surge arrester; tripping accident; voltage 220 kV; Accidents; Area measurement; Heating; Insulators; Lightning; composite insulator; icing flashover prevention; lightning protection; zinc oxide varistor;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
System Science, Engineering Design and Manufacturing Informatization (ICSEM), 2011 International Conference on
Conference_Location :
Guiyang
Print_ISBN :
978-1-4577-0247-1
Type :
conf
DOI :
10.1109/ICSSEM.2011.6081162
Filename :
6081162
Link To Document :
بازگشت