Title :
Improvement of internal charging current compensation for transmission line differential protection
Author :
Yamaura, M. ; Kurosawa, Y. ; Ayakawa, H.
Author_Institution :
Toshiba Corp., Japan
Abstract :
In 1980, a PCM differential relay was developed to allow for the increase in charging current through transmission lines incidental to 1000 kV overhead lines and 500 kV underground cable lines in urban areas. This differential relay compensates the charging current so that the sensitivity of its relay may not decline. The authors first applied a hardware circuit for differential operation of each terminal voltage to compensate the charging current, and then applied a modified differential approximation of self terminal voltage based on numerical calculation to compensate the charging current. The PCM differential relay for transmission lines has been greatly improved in performance, making full use of the advantages of new (second generation in Japan) technology applied to commercial relays
Keywords :
power system protection; 1000 kV; 500 kV; PCM differential relay; differential protection; differential relay; internal charging current compensation; modified differential approximation; overhead lines; performance; self terminal voltage; transmission lines; underground cable lines; urban areas;
Conference_Titel :
Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
Conference_Location :
Nottingham
Print_ISBN :
0-85296-672-5
DOI :
10.1049/cp:19970032