• DocumentCode
    2343419
  • Title

    Improvement of internal charging current compensation for transmission line differential protection

  • Author

    Yamaura, M. ; Kurosawa, Y. ; Ayakawa, H.

  • Author_Institution
    Toshiba Corp., Japan
  • fYear
    1997
  • fDate
    25-27 Mar 1997
  • Firstpage
    74
  • Lastpage
    77
  • Abstract
    In 1980, a PCM differential relay was developed to allow for the increase in charging current through transmission lines incidental to 1000 kV overhead lines and 500 kV underground cable lines in urban areas. This differential relay compensates the charging current so that the sensitivity of its relay may not decline. The authors first applied a hardware circuit for differential operation of each terminal voltage to compensate the charging current, and then applied a modified differential approximation of self terminal voltage based on numerical calculation to compensate the charging current. The PCM differential relay for transmission lines has been greatly improved in performance, making full use of the advantages of new (second generation in Japan) technology applied to commercial relays
  • Keywords
    power system protection; 1000 kV; 500 kV; PCM differential relay; differential protection; differential relay; internal charging current compensation; modified differential approximation; overhead lines; performance; self terminal voltage; transmission lines; underground cable lines; urban areas;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
  • Conference_Location
    Nottingham
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-672-5
  • Type

    conf

  • DOI
    10.1049/cp:19970032
  • Filename
    608138