DocumentCode :
2344580
Title :
Loss of mains detection for embedded generation by system impedance monitoring
Author :
Kane, P.O. ; Fox, B.
Author_Institution :
Queen´´s Univ., Belfast, UK
fYear :
1997
fDate :
25-27 Mar 1997
Firstpage :
95
Lastpage :
98
Abstract :
Embedded generators operating in parallel with the electricity supply network are required by law to fit `loss of mains´ protection. This paper presents a new technique for detecting loss of mains based on the measurement of power system impedance and overcomes the deficiencies of more popular relays. The unit´s decision to trip is based on the identification of the change in impedance that occurs at a private generator´s site when it becomes disconnected from the mains supply
Keywords :
power system protection; embedded generation; loss of mains protection; mains supply disconnection; power system impedance monitoring; private generators; tripping decision;