Abstract :
This paper examines the complications encountered when using distance relays to protect six-phase transmission lines. By examining the impedances seen for various fault conditions, it demonstrates how a full scheme six-phase distance relay and a combination of three phase relays would respond to a variety of short circuit fault conditions
Keywords :
power transmission lines; distance relays; fault conditions; impedance; short circuit fault conditions; six-phase AC transmission lines; six-phase distance relay; three phase relays; transmission lines protection;