DocumentCode
2352023
Title
A positive sequence directional element for numerical distance relays
Author
McLaren, P.G. ; Dirks, E. ; Jayasinghe, R.P. ; Fernando, I. ; Swift, G.W. ; Zhang, Z.
Author_Institution
Manitoba Univ., Winnipeg, Man., Canada
fYear
1997
fDate
25-27 Mar 1997
Firstpage
239
Lastpage
242
Abstract
The technique proposed in this paper uses the ratio of the incremental positive sequence voltage and current phasors to decide direction. This impedance lies in the third quadrant for forward faults and in the first quadrant (not including the origin) for reverse faults. This paper outlines the principle of operation of the new element, describes the integration of the element into a distance relay, then gives results of tests on the relay. The relay was tested first of all on the RTDS, then on-line in two different locations in the Manitoba Hydro network. Finally an off-line model of the relay was tested in a complex series compensation application
Keywords
power system protection; Manitoba Hydro network; RTDS; complex series compensation application; incremental positive sequence current phasor; incremental positive sequence voltage phasor; numerical distance relays; off-line model; on-line testing; positive sequence directional element; real time digital simulator; tests;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
Conference_Location
Nottingham
ISSN
0537-9989
Print_ISBN
0-85296-672-5
Type
conf
DOI
10.1049/cp:19970072
Filename
608191
Link To Document