The aging due to mechanical, thermal, electrical and environmental stresses of a stator insulation system inherently involves alterations of the material properties which are detrimental to its service operation. When these properties are deteriorated to the point where the material can no longer operate safely under normal stress conditions, it implies that it has reached the end of its useful life. To prevent such forced outages and even to improve the useful life, condition-based maintenance and diagnostic tests are periodically conducted on stator insulation system. Among the tests performed to assess the condition of winding insulation, various methods are commonly used like partial discharge measurements, hi-pot, step voltage and ramped voltage tests to name just a few. The I-V curve measured during a ramped direct voltage test, as the one obtained in a polarization/depolarization test, includes the contribution of various current components, the capacitive, the absorption, the surface leakage and the bulk conduction current. But these contributions, especially the absorption and the conduction (surface or volume) currents, are not as easy to separate in a ramped voltage test as in a polarization/depolarization test. So a modeling of the I-V curve obtained with the ramped voltage test, allowing an easy separation of the leakage current from the absorption and the capacitive currents, is presented in this paper. This modeling is compared with field measurements on complete stator windings and with lab measurements on spare coils
Keywords :
ageing; coils; electric generators; insulation testing; leakage currents; machine insulation; machine testing; stators; absorption; aging; condition assessment; condition-based maintenance; conduction current; diagnostic testing; electrical stress; environmental stress; generator I-V curve modeling; mechanical stress; polarization-depolarization testing; ramped direct voltage method; spare coil; stator winding insulation system; surface leakage current; thermal stress; Absorption; Aging; Dielectrics and electrical insulation; Insulation testing; Material properties; Optical polarization; Partial discharge measurement; Stators; Thermal stresses; Voltage;
Conference_Titel :
Electrical Insulation, 2006. Conference Record of the 2006 IEEE International Symposium on
Conference_Location :
Toronto, Ont.
Print_ISBN :
1-4244-0333-2
DOI :
10.1109/ELINSL.2006.1665245