Title :
PD pulse propagation in shielded power cable for symmetric and asymmetric PD pulses
Author :
Oussalah, Naima ; Zebboudj, Youcef ; Boggs, Steven
Author_Institution :
High Voltage Lab., Univ. A.M. of Bejaia
Abstract :
Partial discharge is a useful diagnostic method for a wide range of power apparatus. In the case of shielded power cable, partial discharge can detect workmanship-induced defects in accessories, as well as cavities and electrical trees in the dielectric. Shielded power cables can be considered lossy transmission lines. The high frequency attenuation of the cable causes the peak amplitude of a PD pulse, as well as the pulse energy, to decrease as a function of distance propagated. We develop analytical expressions which characterize the PD pulse propagation in a typical shielded power cable for both symmetric and asymmetric PD pulses for an attenuation constant which increases linearly with frequency, as is normally the case for shielded solid dielectric power cable
Keywords :
cable shielding; partial discharge measurement; power cable insulation; trees (electrical); PD pulse propagation; cable accessories; defect detection; diagnostic method; electrical trees; high frequency attenuation; lossy transmission line; partial discharge; power apparatus; power cable shielding; solid dielectric; Attenuation measurement; Bandwidth; Equations; Fourier transforms; Materials science and technology; Partial discharges; Physics; Power cables; Space vector pulse width modulation; Voltage;
Conference_Titel :
Electrical Insulation, 2006. Conference Record of the 2006 IEEE International Symposium on
Conference_Location :
Toronto, Ont.
Print_ISBN :
1-4244-0333-2
DOI :
10.1109/ELINSL.2006.1665250