Title :
On-line diagnostics of power transformers
Author :
Mentlík, V. ; Prosr, P. ; Pihera, J. ; Polanský, R. ; Trnka, P.
Author_Institution :
Univ. of West Bohemia, Pilsen
Abstract :
A condition of oil-paper insulating system is principal diagnostic indicator for failure-free operation of power transformers. This insulating system is thought to be one of the key components of the whole machine. During the operation of the transformer ageing of the insulating system appears, which may cause changes of its important electrical and mechanical properties. Many factors work simultaneously on the insulation during the operation and the particular effects influence each other as well. The material ageing is also affected by changes of operating properties. Ageing rate of organic components, which compose the insulating system, is mainly accelerated by temperature, humidity and oxygen presence. The diagnostic system, which is mainly applied during the shutdown of the transformer, contributes to the detection of the ageing level and to the judgement of residual working life. Also on-line diagnostic systems are currently more applied, especially for strategically significant devices or in cases, when appeared failure could lead to considerable economic waste. This contribution focuses on analysis of factors causing degradation of insulating system of power transformer as well as on sequent elaboration of programme application for on-line diagnostics of these transformers. Above-mentioned application has been programmed in Lab VIEW graphics environment and provides actions connected with computer analysis, visualization and saving of measured data. The programme also starts alarm in case of overrunning of pre-set limit values and provides approximate estimation of residual working life of device. The main advantage of computing solution of devices consists in the possibility of flexible conformation of sensors and digital indications in accordance to current requirements of particular users
Keywords :
ageing; data visualisation; paper; power engineering computing; power transformer insulation; sensors; transformer oil; Lab VIEW graphics programming; computer analysis; data visualization; digital indication; electrical property; insulation degradation; material ageing; mechanical property; oil-paper insulation condition; on-line diagnostics; organic component; power transformer; sensor; Accelerated aging; Application software; Dielectrics and electrical insulation; Humidity; Mechanical factors; Oil insulation; Power system economics; Power transformer insulation; Power transformers; Temperature;
Conference_Titel :
Electrical Insulation, 2006. Conference Record of the 2006 IEEE International Symposium on
Conference_Location :
Toronto, Ont.
Print_ISBN :
1-4244-0333-2
DOI :
10.1109/ELINSL.2006.1665377