Title :
Determination of particle movement on epoxy coated spacer in 1-Φ Gas insulated busduct
Author :
Padmavathi, D. ; Amarnath, J. ; Kamakshaiah, S.
Author_Institution :
JNTUH, Hyderabad, India
Abstract :
The major threat to Gas insulated Bus duct is presence of metallic particle contamination in the form of loose particles. This may be present on the enclosure, HV conductor or on the spacer. In this paper conducting contaminant trajectory is obtained for particulate on the spacer with SF6 gas dielectric medium. Wire like metallic contaminants of length 10mm with 0.25mm radius of copper, Aluminum and silver are considered to be present on the epoxy coated spacer in 1-Φ GIB with an inner conductor diameter 55mm and an outer enclosure diameter of 152mm.Results are obtained and analyzed for different typical 1-Φ GIS power frequency voltages.
Keywords :
SF6 insulation; aluminium; copper; gas insulated substations; gas insulated switchgear; silver; sulphur compounds; GIS power frequency voltages; HV conductor; SF6; conducting contaminant trajectory; epoxy coated spacer; gas dielectric medium; gas insulated busduct; loose particles; metallic particle contamination; particle movement; size 10 mm; size 152 mm; size 55 mm; Aluminum; Conductors; Copper; Ducts; Electric fields; Geographic Information Systems; Sulfur hexafluoride;
Conference_Titel :
Power Modulator and High Voltage Conference (IPMHVC), 2010 IEEE International
Conference_Location :
Atlanta, GA
Print_ISBN :
978-1-4244-7131-7
DOI :
10.1109/IPMHVC.2010.5958395