DocumentCode
236890
Title
Surge voltage and environmental electromagnetic field analysis for HV composite transmission tower under lightning strokes
Author
Youpeng Huangfu ; Shuhong Wang ; Xi Tao ; Song Wang ; Bin Yang ; Guolin Wang ; Yuxi Zhang
Author_Institution
Fac. of Electr. Eng., State Key Lab. of Electr. Insulation & Power Equip., Xi´an Jiaotong Univ., Xi´an, China
fYear
2014
fDate
4-8 Aug. 2014
Firstpage
445
Lastpage
450
Abstract
In this paper, the surge voltages of grounding system for a 330 kV high voltage (HV) composite transmission tower under lightning strokes are comprehensively presented. An equivalent distributed parameter model of the tower is established to investigate the lightning overvoltage by using EMTP program. The distributed capacitances among the adjacent two layers of cross arms, the capacitances between the lines and grounding ladders are calculated by using three dimensional (3D) Finite Element Method (FEM). The wave impedances of the ground wire cross arm, grounding ladder, and metallic tower body are determined by using the analytic equations. The lightning overvoltage calculation and comparison are conducted considering the diverse grounding configurations, such as the single-, double-, and three-ladder grounding systems. The influence of the radius of the grounding ladder on the overvoltage characteristics is analyzed. The proper grounding ladder system is determined so that the voltage between ladder and transmission lines is less than the flashover initial voltage of the cross arm. In order to evaluate the electromagnetic environment around the tower, the induced electromagnetic field at the level of 1.5 m above the ground is computed by 3D FEM. The simulated results suggest that the electric field intensity is much greater than the safety threshold of electric field intensity around the transmission lines.
Keywords
earthing; electric fields; finite element analysis; flashover; lightning protection; overvoltage protection; poles and towers; power transmission lines; safety; 3D FEM; EMTP program; HV composite transmission tower; distributed capacitances; double-ladder grounding systems; electric field intensity; electromagnetic environment; environmental electromagnetic field analysis; equivalent distributed parameter model; ground wire cross arm; grounding ladders; grounding system; high voltage composite transmission tower; lightning overvoltage; lightning strokes; overvoltage characteristics; safety threshold; single-ladder grounding systems; surge voltage; three dimensional finite element method; three-ladder grounding systems; transmission lines; voltage 330 kV; Capacitance; Flashover; Grounding; Lightning; Poles and towers; Voltage control; Wires; Composite Transmission Tower; FEM; Lightning Surge Overvoltage; Surge Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility (EMC), 2014 IEEE International Symposium on
Conference_Location
Raleigh, NC
Print_ISBN
978-1-4799-5544-2
Type
conf
DOI
10.1109/ISEMC.2014.6899013
Filename
6899013
Link To Document