Abstract
This paper presents a shunt active power filter control circuit for a four-wire three-phase supply network. The active power filter is implemented with a four-wire three-phase PWM voltage converter connected to the AC mains with neutral conductor. The neutral is connected to the middle point of two capacitors in series on the converter DC side. Its AC currents are controlled with a generalised space vector based hysteresis current controller in the αβ0 coordinate system. The active power filter compensates current harmonics of positive, negative and zero sequence so that the mains currents constitute a first harmonic positive sequence system. These current harmonics are determined in the Park´s referential, whose transformation angle is calculated with a phase locked loop controller
Keywords
power filters; αβ0 coordinate system; AC currents control; AC mains; Park´s referential; capacitors; converter DC side; current harmonics compensation; four wire active power filter control; four-wire three-phase PWM voltage converter; four-wire three-phase supply network; negative sequence harmonics; neutral conductor; phase angle determination; phase locked loop; positive sequence harmonics; shunt active power filter control circuit; space vector based hysteresis current controller; transformation angle calculation; zero sequence harmonics;
fLanguage
English
Publisher
iet
Conference_Titel
Power Electronics and Variable Speed Drives, 1998. Seventh International Conference on (Conf. Publ. No. 456)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-704-7
Type
conf
DOI
10.1049/cp:19980496
Filename
732009
Link To Document