DocumentCode
2376871
Title
Surge protection of a large medium voltage motor-a case study
Author
Sutherland, Peter E.
Author_Institution
GE Power Syst., Schenectady, NY, USA
fYear
1997
fDate
11-16 May 1997
Firstpage
36
Lastpage
40
Abstract
The raw mill motor in a cement mill had been damaged by repeated switching surges and subsequently rewound. New arresters were placed on the motor at that time. The surges coming in to the motor were measured, and the surge protection was reviewed. It was found that the original gapped silicon carbide surge arresters on the motor had insufficient protective margin, while the new zinc oxide arresters provided an adequate margin. The operation of the surge capacitors in protecting the motor was analyzed. Surge protection and insulation coordination should be reviewed in comprehensive power system studies
Keywords
arresters; cement industry; electric motors; industrial power systems; insulation co-ordination; motor protection; power system protection; power system transients; MV motor surge protection; ZnO; ZnO surge arresters; case study; cement mill power systems; insulation coordination; protective margin; raw mill motor; surge capacitors; surge measurements; switching surges; Arresters; Capacitors; Insulation; Medium voltage; Milling machines; Power system protection; Silicon carbide; Surge protection; Surges; Zinc oxide;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial and Commercial Power Systems Technical Conference, 1997. Conference Record, Papers Presented at the 1997 Annual Meeting., IEEE 1997
Conference_Location
Philadelphia, PA
Print_ISBN
0-7803-3825-1
Type
conf
DOI
10.1109/ICPS.1997.595985
Filename
595985
Link To Document