DocumentCode :
2376990
Title :
Impact of distribution system quality on DG interconnection protection
Author :
Cho, Sung-Min ; Shin, Hee-Sang ; Kim, Jae-Chul
Author_Institution :
Dept. of Electr. Eng., Soongsil Univ., Seoul, South Korea
fYear :
2010
fDate :
25-29 July 2010
Firstpage :
1
Lastpage :
4
Abstract :
This paper has analyzed the impact of distribution power quality, especially unbalancing and triplen harmonic, on DG interconnection protection. We explored that the unbalanced single phase loads increase neutral current at DG interconnect transformer by analysis of measured data and simulation of PSCAD/EMTDC. An impact of triplen harmonic on DG interconnection transformers which are grounded wye (utility)-delta (DG) was also studied in same method. We confirmed that the power quality should be considered carefully for setting of ground overcurrent trip pick up level.
Keywords :
data analysis; load (electric); power distribution protection; power supply quality; power system harmonics; power system simulation; power transformer protection; DG interconnect transformer; DG interconnection protection; PSCAD-EMTDC simulation; data analysis; distribution power quality; distribution system quality; grounded wye delta; neutral current; triplen harmonic; unbalanced single phase load; DG Interconnection; Neutral Current; Triplen Harmonics; Voltage Unbalance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location :
Minneapolis, MN
ISSN :
1944-9925
Print_ISBN :
978-1-4244-6549-1
Electronic_ISBN :
1944-9925
Type :
conf
DOI :
10.1109/PES.2010.5589431
Filename :
5589431
Link To Document :
بازگشت