Abstract
In this paper we address the problem of placing Phasor Measurement Units (PMUs) on a long transmission line connecting two areas of a power system network. Dynamic measurements of electrical signals such as magnitudes and phases of bus voltages and line currents, corrupted with Gaussian noise, are available from these PMUs. Our objective is to determine the best locations for their placement such that, given a particular measured noisy signal, the error in identifying a two-machine interarea equivalent model of the two-area power system is minimum. We first show that the identification problem is equivalent to estimating four essential model parameters, namely the two intra-area reactances, and the inertias of the two aggregated machines. We then formulate the Cramer-Rao bounds for the estimates of these four unknown parameters, and show that the bounds are functions of the PMU location. We finally state the condition for finding the optimal PMU location to achieve the tightest Cramer-Rao bound.
Keywords
phase measurement; power system measurement; power transmission lines; Cramer-Rao bound estimation; PMU optimal placement; error identification; noisy measurement data; phaser measurement units; power system network; transmission lines; two-machine interarea equivalent model; Cramer-Rao bound; Phasor measurements; parameter estimation; swing equation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589445
Filename
5589445
Link To Document