DocumentCode
2377277
Title
Application of polarization based measurement techniques for diagnosis of field transformers
Author
Ekanayake, C. ; Saha, T.K. ; Ma, H. ; Allan, D.
Author_Institution
Sch. of ITEE, Univ. of Queensland, St. Lucia, QLD, Australia
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
8
Abstract
This paper presents both quantitative and qualitative analysis of several polarization based measurements, which include frequency domain spectroscopy (FDS) and polarization depolarization current (PDC) measurements on four different field transformers. The X-Y model and the RC circuit model are mainly used in the analyses. In this study sequential FDS/PDC measurements on the same unit are used to identify the progressive change of the insulation condition. Influence of oil conductivity and geometrical parameters on the estimates from FDS response is shown in detail. Based on this study a simple technique to improve the reliability from FDS measurement is discussed. Influence of the oil refurbishment process on polarization based measurements is also presented and discussed.
Keywords
chemical analysis; polarisation; power transformer insulation; reliability; RC circuit model; field transformer diagnosis; frequency domain spectroscopy; oil refurbishment process; polarization based measurement techniques; polarization depolarization current; qualitative analysis; quantitative analysis; Frequency domain spectroscopy; insulation ageing; insulation response modeling; moisture estimation; oil conductivity; polarization depolarization current; transformer insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589446
Filename
5589446