Title :
Fault Location Using Sparse Voltage Measurements
Author_Institution :
Univ. of Kentucky, Lexington
fDate :
Sept. 30 2007-Oct. 2 2007
Abstract :
This paper presents a general method for pinpointing location of fault on a transmission line by employing only voltage measurements on any bus for any type of fault and taking advantage of bus impedance matrix technique. The approach assumes that the network data is available. Possible scenarios where prefault measurements are not available, and scenarios where only voltage magnitude is available, are considered.
Keywords :
fault diagnosis; impedance matrix; power transmission faults; power transmission lines; voltage measurement; fault location; impedance matrix technique; sparse voltage measurements; transmission line; Fault location; Impedance measurement; Iterative methods; Power system reliability; Power system restoration; Power transmission lines; Sparse matrices; Transmission line matrix methods; Transmission line measurements; Voltage measurement; Fault location; bus impedance matrix; transmission line; voltage measurement;
Conference_Titel :
Power Symposium, 2007. NAPS '07. 39th North American
Conference_Location :
Las Cruces, NM
Print_ISBN :
978-1-4244-1726-1
Electronic_ISBN :
978-1-4244-1726-1
DOI :
10.1109/NAPS.2007.4402278