• DocumentCode
    2377325
  • Title

    A Novel PMU-Based Transmission Line Protection Scheme Design

  • Author

    Khorashadi-Zadeh, Hassan ; Li, Zuyi

  • Author_Institution
    Illinois Inst. of Technol., Chicago
  • fYear
    2007
  • fDate
    Sept. 30 2007-Oct. 2 2007
  • Firstpage
    13
  • Lastpage
    19
  • Abstract
    This paper presents an adaptive transmission line protection scheme based on synchronized phasor measurement. This scheme uses the positive-sequence voltage and current phasors at both ends of a transmission line to determine the parameter of the transmission line and the location of a fault on the transmission line. This scheme can be used for the protection of both single-and double-circuit transmission lines. This scheme is also robust against power swing conditions. A novel adaptive single pole auto re-closer is introduced based on the proposed scheme due to its capability of differentiating transient and permanent faults. System simulation studies show that the proposed scheme is able to operate fast and accurately for transmission line protection.
  • Keywords
    power system measurement; power transmission protection; PMU; adaptivepower transmission line protection scheme; current phasors; positive sequence voltage; power swing conditions; synchronized phasor measurement; Circuit faults; Global Positioning System; Integrated circuit modeling; Phasor measurement units; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Transmission line measurements; Virtual reality; Global Positioning System (GPS); Phasor Measurement Unit; Transmission Line Protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Symposium, 2007. NAPS '07. 39th North American
  • Conference_Location
    Las Cruces, NM
  • Print_ISBN
    978-1-4244-1726-1
  • Electronic_ISBN
    978-1-4244-1726-1
  • Type

    conf

  • DOI
    10.1109/NAPS.2007.4402279
  • Filename
    4402279