• DocumentCode
    2378694
  • Title

    Analysis of High Voltage Harmonic Distortion Measurements

  • Author

    Etezadi-Amoli, M. ; Choma, K. ; Louie, R.

  • Author_Institution
    UNR, Reno
  • fYear
    2007
  • fDate
    Sept. 30 2007-Oct. 2 2007
  • Firstpage
    511
  • Lastpage
    517
  • Abstract
    This paper provides a set of harmonic measurements at a 25 kV distribution feeder. The work was requested by a large industrial customer. A utility grade harmonic meter was used for the measurements. The data was obtained at the point of common coupling where the utility primary meters were installed. The IEEE 519 standard is used to analyze the results and solutions for improving the utility supply system are presented. It is also shown that erroneous TDD measurements can be obtained using standard measuring equipment.
  • Keywords
    harmonic distortion; power distribution; power system harmonics; power system measurement; 25 kV distribution feeder; IEEE 519 standard; TDD measurements; common coupling; high voltage harmonic distortion measurements analysis; utility grade harmonic meter; Distortion measurement; Electrical engineering; Electrical equipment industry; Harmonic analysis; Harmonic distortion; Hydroelectric power generation; Measurement standards; Reactive power; Substations; Voltage measurement; Distribution Systems; TDD; THD; Voltage and Current Harmonic Measurements;