Abstract :
The purpose of this study is to develop a method to measure untransposed transmission line parameters for protection relay setting. For relaying schemes such as distance relays, current differential relays and fault locators, it is very useful to ascertain the precise setting values in service, without the need for setting calculations prior to installation, and also for the relays to be able to adaptively change their settings as the system configuration changes. This paper describes a method of live line measurement of the parameters of an untransposed three phase one circuit transmission line and untransposed two parallel transmission lines and necessary conditions to measure line parameters. We propose a mathematical approach using synchronous voltages and line currents at both ends of the line in different states, where two models, the equivalent PI circuit and distributed constant line, are employed. For two parallel transmission lines, applying a mode decomposition, we show that two parallel transmission lines can be transformed into double independent three phase circuits. The efficiency and issues are shown using several simulation examples in MATLAB.
Keywords :
matrix algebra; power system measurement; power transmission lines; power transmission protection; relay protection; MATLAB; current differential relays; distance relays; distributed constant line; double independent three phase circuits; equivalent PI circuit; fault locators; live line measurement; mathematical approach; mode decomposition; protection relay setting; synchronous voltages; untransposed three phase transmission line parameters; untransposed two parallel transmission lines; MAT-LAB; Synchrophasor; Transmission line; adaptive relay; fault location; line parameter; protection relay; untransposed line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location :
Minneapolis, MN
ISSN :
1944-9925
Print_ISBN :
978-1-4244-6549-1
Electronic_ISBN :
1944-9925
Type :
conf
DOI :
10.1109/PES.2010.5589579
Filename :
5589579
Link To Document :
بازگشت