DocumentCode :
2380674
Title :
Current differential protection of transmission line using the moving window averaging technique
Author :
Dambhare, Sanjay ; Soman, Shreevardhan ; Chandorkar, Mukul
Author_Institution :
Coll. of Eng., Pune, India
fYear :
2010
fDate :
25-29 July 2010
Firstpage :
1
Lastpage :
1
Abstract :
We propose a new approach to current differential protection of transmission lines. In this approach, we transform the instantaneous line current(s) by using a moving window averaging technique. If the time span of moving window is equal to one-cycle time, then the steady-state value of the transformed current is zero for a periodic signal which is composed of fundamental and harmonic frequencies. Signal distortions (e.g., a fault) cause the transformed currents to deviate from the nominal zero value. This permits the development of a sensitive, secure, fast, and yet simple current differential protection scheme. The scheme can be applied in toto to series-compensated transmission lines. Results on a four-machine ten-bus system and comparative evaluation with state-of-the-art methods brings out promise of the proposed method.
Keywords :
power transmission lines; power transmission protection; comparative evaluation; current differential protection; four-machine ten-bus system; instantaneous line current; moving window averaging; series compensated transmission lines; signal distortions; state-of-the-art methods; steady-state value; transformed current; window averaging technique;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location :
Minneapolis, MN
ISSN :
1944-9925
Print_ISBN :
978-1-4244-6549-1
Electronic_ISBN :
1944-9925
Type :
conf
DOI :
10.1109/PES.2010.5589638
Filename :
5589638
Link To Document :
بازگشت