DocumentCode
2382214
Title
Coordination of overexcitation limiter, field overcurrent protection and generator control
Author
Pajuelo, Eli ; Gokaraju, Ramakrishna ; Sachdev, M.S.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Saskatchewan, Saskatoon, SK, Canada
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
7
Abstract
The overexcitation limit of synchronous generator plays an important role in the voltage stability of power systems. Achieving maximum use of the overexcitation capability requires adequate coordination between generator control and protection. This paper provides an example of coordination between overexcitation limiter (OEL), field overcurrent protection and automatic voltage regulator (AVR) for a synchronous generator. The coordination achieved is then verified by a model simulation using an electromagnetic transient program for practical scenarios of interest. Suggested modifications to the ST1A type exciter model are presented to represent the complete functionality of the OEL function.
Keywords
EMTP; current limiters; machine control; machine protection; overcurrent protection; synchronous generators; voltage regulators; automatic voltage regulator; electromagnetic transient program; field overcurrent protection; model simulation; overexcitation limiter coordination; synchronous generator control; voltage stability; Over excitation limiter (OEL); excitation controls; generator controls; synchronous machines;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589734
Filename
5589734
Link To Document