DocumentCode
2384391
Title
A New Measurement Method of the Dynamic Contact Resistance of HV Circuit Breakers
Author
Laundry, M. ; Mercier, A. ; Ouellet, G. ; Rajotte, C. ; Caron, J. ; Roy, M. ; Brikei, F.
Author_Institution
Hydro-Quebec, Que.
fYear
2006
fDate
21-24 May 2006
Firstpage
1002
Lastpage
1009
Abstract
The proposed paper presents a new dynamic-contact-resistance measurement method that has been validated by field tests which were performed on air-blast and SF6 gas circuit breakers. The unique measurement method allows reproducible resistance curves to be obtained, which is not the case with the conventional method. Dynamic contact resistance curves obtained by using both the conventional technique and the new method are compared. By applying the novel measuring method, the dynamic contact resistance curve is easy to interpret. It is believed that the new measuring method can be used as a diagnostic tool for SF6 gas circuit breakers whenever contact anomalies are suspected. This new measurement method allows for an accurate evaluation of both main- and arcing-contact conditions without dismantling the circuit breaker. Moreover, it provides the maintenance crew with relevant criteria for selecting the interrupting chambers that should be internally inspected
Keywords
SF6 insulation; air blast circuit breakers; arcs (electric); HV circuit breakers; SF6 gas circuit breakers; air-blast circuit breakers; arcing-contact conditions; dynamic contact resistance measurement; measurement method; Circuit breakers; Circuit testing; Contact resistance; Current measurement; Electrical resistance measurement; Noise measurement; Performance evaluation; Sulfur hexafluoride; Time domain analysis; Time measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES
Conference_Location
Dallas, TX
Print_ISBN
0-7803-9194-2
Type
conf
DOI
10.1109/TDC.2006.1668639
Filename
1668639
Link To Document