• DocumentCode
    2384426
  • Title

    Tracking the Eastern Interconnection frequency governing characteristic

  • Author

    Ingleson, James W. ; Allen, Eric

  • Author_Institution
    RLC Eng., Altamont, NY, USA
  • fYear
    2010
  • fDate
    25-29 July 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The Eastern Interconnection frequency governing characteristic, sometimes called Beta, has been tracked by one of the authors for a period of more than 15 years. While there are some errors inherent to the process followed, we believe that the errors do not obscure the overall trend. We have found that Beta has been declining and has reached a level of approximately 25 MW/mHz. This has important implications in system behavior, particularly in situations involving islanding. Study assumptions need to reflect this observed reduction in governing response.
  • Keywords
    power system interconnection; Eastern interconnection frequency governing characteristic; frequency response; load governing; Beta; Combined frequency governing characteristic; Frequency Governing Characteristic; Frequency Response; Generation Governing; Load Governing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting, 2010 IEEE
  • Conference_Location
    Minneapolis, MN
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-6549-1
  • Electronic_ISBN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PES.2010.5589872
  • Filename
    5589872