A Study on SFCL Systems for Korean Power System Application
Author
Lee, Seung Ryul ; Kim, Jong Yul ; Yoon, Jae Young
Author_Institution
Korea Electrotechnol. Res. Inst., Changwon
fYear
2006
fDate
21-24 May 2006
Firstpage
1144
Lastpage
1148
Abstract
The recovery time of developing SFCL (superconducting fault current limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the progress of SFCL technology is considered. However, auto-reclosing time of circuit breaker is 0.3 sec in Korean power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes two new SFCL systems for power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLs
Keywords
circuit breakers; fault current limiters; power system protection; superconducting devices; Korean power system application; circuit breaker; power system protection; superconducting fault current limiter; Circuit breakers; Fault current limiters; Fault currents; Power system faults; Power system interconnection; Power system protection; Power system reliability; Power system stability; Power systems; Superconducting transmission lines;