For a successful ASD installation . . .look beyond the electronics
Author
Nailen, R.L.
Author_Institution
Wisconsin Electr. Power Co., Milwaukee, WI, USA
fYear
1991
fDate
6-9 May 1991
Firstpage
43
Lastpage
48
Abstract
Electrical and mechanical design of drive components must suit wiring practices based on recognized industry standards. Safety grounding, medium voltage cable termination, cable training, and electrical clearances are discussed using power plant fan installations in a particular power plant as a case study. The design shortcomings found during the installation of several large 4 kV drives and the corrective actions taken (including the revision of specifications for later drive projects) are explained
Keywords
earthing; electric connectors; installation; safety; variable speed drives; 4 kV; MV cable termination; adjustable speed drives; cable training; electrical clearances; electrical design; industry standards; mechanical design; power plant fan installations; safety grounding; wiring practices; Electrical safety; Frequency; Grounding; Inverters; Medium voltage; Power cables; Power generation; Power system planning; Synchronous motors; Variable speed drives;