DocumentCode
2385435
Title
Modeling Stalled Induction Motors
Author
Chinn, Garry L.
Author_Institution
Southern California Edison, Rosemead, CA
fYear
2006
fDate
21-24 May 2006
Firstpage
1325
Lastpage
1328
Abstract
Southern California Edison experienced a slow voltage recovery event in summer of 2004 attributed to stalled air conditioning compressor motors. Simulations using existing load models was not able to reproduce the voltages recorded during the event. Based on tests of a four ton residential air conditioning unit a new model was developed to mimic the stall behavior of induction motors in order to replicate the voltage observed
Keywords
air conditioning; compressors; induction motors; induction motor modelling; residential air conditioning compressor motors; voltage recovery event; Air conditioning; Discrete event simulation; Impedance; Induction motors; Load modeling; Low voltage; Predictive models; Substations; Temperature; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES
Conference_Location
Dallas, TX
Print_ISBN
0-7803-9194-2
Type
conf
DOI
10.1109/TDC.2006.1668703
Filename
1668703
Link To Document