• DocumentCode
    2387194
  • Title

    Feasibility analysis of transformer winding DC resistance measuring on-line

  • Author

    Li, Baoshu ; Guo, Yu ; Zhao, Shutao

  • Author_Institution
    State Key Lab. of Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Baoding, China
  • fYear
    2012
  • fDate
    19-20 May 2012
  • Firstpage
    568
  • Lastpage
    571
  • Abstract
    In this paper, several existing measurement methods on transformer winding direct current (DC) resistance are introduced, and its shortcomings are also analyzed. Through transformer winding DC resistance measuring experiments with AC power supply, which separated iron core loss form winding copper loss in transformer by adopting power separation, and then the DC resistance can be calculated based copper loss and the winding current. The measuring results show that transformer winding DC resistance can be derived in AC power condition, and the DC resistance measurement online can be realized.
  • Keywords
    electric resistance measurement; losses; power transformers; transformer cores; transformer windings; AC power supply; feasibility analysis; iron core loss; online DC resistance measurement; power separation; transformer winding; winding copper loss; Current measurement; Electrical resistance measurement; Loss measurement; Power measurement; Resistance; Voltage measurement; Windings; DC resistance; online measurement; transformer winding;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Systems and Informatics (ICSAI), 2012 International Conference on
  • Conference_Location
    Yantai
  • Print_ISBN
    978-1-4673-0198-5
  • Type

    conf

  • DOI
    10.1109/ICSAI.2012.6223061
  • Filename
    6223061