Application of hydrogenated water to future cooling system
Author
Yokoi, Ikunori ; Yamazaki, Yoshio ; Abe, Toshikazu ; Ohmi, Tadahiro
Author_Institution
New Ind. Creation Hatchery Center (NICHe), Tohoku Univ., Sendai, Japan
fYear
2000
fDate
2000
Firstpage
297
Lastpage
300
Abstract
This study was carried on to contribute the application of hydrogenated water to a future cooling water system. In order to much improve cost of ownership (CoO) of cooling water, we firstly introduced hydrogenated city water to the cooling water system. Compared to a hydrogenated ultrapure water (H2-UPW), it has a high pH value, resulting in it having a low oxidation-reduction potential (ORP) value so that it has the characteristics of flowing out suppression on even the surface of an iron pipeline. This application, based on control of pH and ORP value in water, is a candidate for future cooling water system to achieve initial and running cost reduction as well as ESH (environment, safety and health) promotion
Keywords
air conditioning; cooling; oxidation; pH; water; ESH; H2O; ORP value; cooling system; cooling water system; cost of ownership; hydrogenated ultrapure water; hydrogenated water; oxidation-reduction potential; pH control; Building materials; Cities and towns; Conductivity; Cooling; Copper; Costs; Health and safety; Iron; Pipelines; Steel;
fLanguage
English
Publisher
ieee
Conference_Titel
Semiconductor Manufacturing, 2000. Proceedings of ISSM 2000. The Ninth International Symposium on
Conference_Location
Tokyo
ISSN
1523-553X
Print_ISBN
0-7803-7392-8
Type
conf
DOI
10.1109/ISSM.2000.993672
Filename
993672
Link To Document