Abstract :
In this paper calculated field intensities in gas-insulated substations (GIS) are investigated. The existence and importance of areas with low field density for three-phase GIS are shown by means of specific utilization factors. Effects of these characteristic properties are discussed with respect to their influence on particle movement. Therefore, calculated and observed two-dimensional trajectories of moving particles complete this study. As an evident result which is also supported by PD measurements, the particle movement is minor for three-phase enclosures. The experimental set-up and the test-vessel are described
Keywords :
gas insulated substations; insulator contamination; electric field; gas insulated substation; metal enclosure; particulate contamination; three-phase GIS; two-dimensional particle trajectory; Conductors; Geographic Information Systems; Motion measurement; Particle measurements; Power generation economics; Power transmission; Stress; Substations; Testing; Voltage;