• DocumentCode
    2388742
  • Title

    Free moving particles in three-phase metal enclosed GIS

  • Author

    Knapp, M. ; Feser, K. ; Rees, V.

  • Author_Institution
    Inst. of Power Transmission & High Voltage Technol., Stuttgart Univ., Germany
  • fYear
    1998
  • fDate
    25-28 Oct 1998
  • Firstpage
    497
  • Abstract
    In this paper calculated field intensities in gas-insulated substations (GIS) are investigated. The existence and importance of areas with low field density for three-phase GIS are shown by means of specific utilization factors. Effects of these characteristic properties are discussed with respect to their influence on particle movement. Therefore, calculated and observed two-dimensional trajectories of moving particles complete this study. As an evident result which is also supported by PD measurements, the particle movement is minor for three-phase enclosures. The experimental set-up and the test-vessel are described
  • Keywords
    gas insulated substations; insulator contamination; electric field; gas insulated substation; metal enclosure; particulate contamination; three-phase GIS; two-dimensional particle trajectory; Conductors; Geographic Information Systems; Motion measurement; Particle measurements; Power generation economics; Power transmission; Stress; Substations; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
  • Conference_Location
    Atlanta, GA
  • Print_ISBN
    0-7803-5035-9
  • Type

    conf

  • DOI
    10.1109/CEIDP.1998.732944
  • Filename
    732944