    Partial discharge characteristics in aged EPR, 15 kV rated cables

  • Author

    Ahmed, Nezar ; Srinivas, Nagu

  • Author_Institution
    Detroit Edison Co., MI, USA
  • fYear
    1998
  • fDate
    25-28 Oct 1998
  • Firstpage
    512
  • Abstract
    Several 15-kV rated, EPR cables subjected to aging processes were examined for partial discharge (PD). These cables were subjected to different load cycling while fully immersed in water to obtain different aging conditions. PD initiated in these cables then was measured at rated and elevated voltages. Correlation then was examined between the PD signature and the type of insulation defect. This achieved by comparing the PD frequency, magnitude and phase angles of different insulation defects. Correlation between the PD level and the ac-breakdown voltage of these cables also was presented in this paper. The same investigations also were repeated on several cables removed from service after 15-20 years of service
  • Keywords
    ageing; electric breakdown; ethylene-propylene rubber; partial discharges; power cable insulation; 15 kV; AC breakdown; EPR; aging; insulation defect; load cycling; partial discharge; power cable; water immersion; Aging; Cables; Conductors; Frequency; Insulation; Paramagnetic resonance; Partial discharge measurement; Partial discharges; Testing; Voltage;