Partial discharge characteristics in aged EPR, 15 kV rated cables
Author
Ahmed, Nezar ; Srinivas, Nagu
Author_Institution
Detroit Edison Co., MI, USA
fYear
1998
fDate
25-28 Oct 1998
Firstpage
512
Abstract
Several 15-kV rated, EPR cables subjected to aging processes were examined for partial discharge (PD). These cables were subjected to different load cycling while fully immersed in water to obtain different aging conditions. PD initiated in these cables then was measured at rated and elevated voltages. Correlation then was examined between the PD signature and the type of insulation defect. This achieved by comparing the PD frequency, magnitude and phase angles of different insulation defects. Correlation between the PD level and the ac-breakdown voltage of these cables also was presented in this paper. The same investigations also were repeated on several cables removed from service after 15-20 years of service
Keywords
ageing; electric breakdown; ethylene-propylene rubber; partial discharges; power cable insulation; 15 kV; AC breakdown; EPR; aging; insulation defect; load cycling; partial discharge; power cable; water immersion; Aging; Cables; Conductors; Frequency; Insulation; Paramagnetic resonance; Partial discharge measurement; Partial discharges; Testing; Voltage;